UKH(K)-630 Thermal Overload Relay

Customization:
Available
Usage:
Household Appliances Relay, Communication Relay
Size:
Miniature
Frequency:
50/60Hz
Theory:
Thermal Relay
Protective Characteristics:
Open Relay
Rated Insulation Voltage:
660V
Rated Working Current:
0.1A---93A

1. The thermal relays also provide temperature compensation, action indication, automatic and manual reset, stop, and testing functions. The products are characterized by stable and reliable performance. The thermal relays can be plugged into contactors or installed indepe-ndently.Compliant standards: IEC/EN 60947-4-1, IEC/EN 60947-5-1.

2. Motion Characteristic: Three-phase Balance Motion Time

No Times of the setting current Motion time Start condition Ambient temperature
1 1.05 >2h Cold state 20±5oC
2 1.2 <2h Heat state(Following the No.1 test)
3 1.5 <4min
4 7.2 10A 2s< Tp≤10s ≤63A Cold state
10 4s< Tp≤10s >63A

3. Phase-losing Motion Characteristic

No Times of the setting current Motion time Start condition Ambienttemperature
Any two phases Another phase
1 1.0 0.9 >2h Cold state 20±5oC
2 1.15 0 <2h Heat state(Following the No.1 test)

4. Specification

pe Rated working current of
thermal relay
Thermal component
Scale of rated current(A)
1-13 25 1301 0.10-0.16
1302 0.16-0.25
1303 0.25-0.40
1304 0.40-0.63
1305 0.63-1.0
1306 1.0-1.6
13×6 1.25-2.0
1307 1.6-2.5
1308 2.5-4.0
1310 4.0-6.0
1312 5.5-8.0
1314 7.0-10.0
1316 9.0-13.0
1321 12.0-18.0
1322 17.0-25.0
1-23 36 2353 23.0-32.0
2255 28.0-36.0
1-33 93 3353 23.0-32.0
3355 30.0-40.0
3357 37.0-50.0
3359 48.0-65.0
3361 55.0-70.0
3363 63.0-80.0
3365 80.0-93.0

This site uses cookies

We use cookies to collect information about how you use this site. We use this information to make the website work as well as possible and improve our services.