UKH(K)-22 Thermal Overload Relay
- Customization:
- Available
- Usage:
- Household Appliances Relay, Communication Relay
- Size:
- Miniature
- Frequency:
- 50/60Hz
- Theory:
- Thermal Relay
- Protective Characteristics:
- Open Relay
- Rated Insulation Voltage:
- 660V
- Rated Working Current:
- 0.1A---93A
1. The thermal relays also provide temperature compensation, action indication, automatic and manual reset, stop, and testing functions. The products are characterized by stable and reliable performance. The thermal relays can be plugged into contactors or installed indepe-ndently.Compliant standards: IEC/EN 60947-4-1, IEC/EN 60947-5-1.
2. Motion Characteristic: Three-phase Balance Motion Time
No | Times of the setting current | Motion time | Start condition | Ambient temperature | ||
1 | 1.05 | >2h | Cold state | 20±5oC | ||
2 | 1.2 | <2h | Heat state(Following the No.1 test) | |||
3 | 1.5 | <4min | ||||
4 | 7.2 | 10A | 2s< Tp≤10s | ≤63A | Cold state | |
10 | 4s< Tp≤10s | >63A |
3. Phase-losing Motion Characteristic
No | Times of the setting current | Motion time | Start condition | Ambienttemperature | |
Any two phases | Another phase | ||||
1 | 1.0 | 0.9 | >2h | Cold state | 20±5oC |
2 | 1.15 | 0 | <2h | Heat state(Following the No.1 test) |
4. Specification
pe | Rated working current of thermal relay |
Thermal component Scale of rated current(A) |
|
1-13 | 25 | 1301 | 0.10-0.16 |
1302 | 0.16-0.25 | ||
1303 | 0.25-0.40 | ||
1304 | 0.40-0.63 | ||
1305 | 0.63-1.0 | ||
1306 | 1.0-1.6 | ||
13×6 | 1.25-2.0 | ||
1307 | 1.6-2.5 | ||
1308 | 2.5-4.0 | ||
1310 | 4.0-6.0 | ||
1312 | 5.5-8.0 | ||
1314 | 7.0-10.0 | ||
1316 | 9.0-13.0 | ||
1321 | 12.0-18.0 | ||
1322 | 17.0-25.0 | ||
1-23 | 36 | 2353 | 23.0-32.0 |
2255 | 28.0-36.0 | ||
1-33 | 93 | 3353 | 23.0-32.0 |
3355 | 30.0-40.0 | ||
3357 | 37.0-50.0 | ||
3359 | 48.0-65.0 | ||
3361 | 55.0-70.0 | ||
3363 | 63.0-80.0 | ||
3365 | 80.0-93.0 |